Dn-4867:b. 03/27/09 — Page 1 of 4 UDACT Universal Digital Alarm Communicator Transmitter Annunciator Control Systems dn-4867:b. D-160 General The Universal Digital Alarm Communicator Transmitter (UDACT) is designed for use on the Notifier NFS-320, NFS2- 640, NFS2-3030, NFS-640 and NFS-3030 Fire Alarm Control Panels and on the NCA-2 and NCA Network Control Annunci- ator. When used in conjunction with the NCA-2 network con- trol annunciators the UDACT can report the status of all control panels on NOTI.FIRE.NET™. The UDACT transmits system status to UL listed Central Station Receivers via the public switched telephone network. NOTE: The UDACT can also be used with legacy panels.
Please refer to the UDACT manual for more information. The UDACT is compact in size and may be mounted externally in a separate cabinet. EIA-485 annunciator communications bus and regulated 24-volt connections are required. The UDACT is capable of transmitting the status of software zones (Alarm and Trouble), System Trouble, Panel Off-Normal, Supervisory, Bell Trouble, Low Battery, and AC Fail.
The UDACT is capable of transmitting all of the zone and point sta- tus associated with each panel. When the UDACT is used with the, NFS-3030, NFS2-3030, and NCA-2 it is capable of reporting up to 2,040 points. Reporting may be in the form of points or zones (refer to the UDACT manual for specific reporting parameters). The first 568 points transmitted may be programmed for a variety of types, including fire, waterflow, supervisory, etc. Remaining points transmitted are for fire alarm only.
1967 buick skylark gs repair manual. NOTE: Descriptions regarding point capacity, listed above, are for receivers which receive in Ademco Contact ID format. See chart on page 2 for compatible receivers. Features.
Maximum of 14 point trouble messages transmitted per hour. Dual phone lines. Dual telephone line voltage detect. Surface Mount Technology. Compact in size: 6.75' x 4.25' (17.145 x 10.795 cm). Built-in programmer.
Notifier Installation Manual
Built-in 4-character red 7-segment LED display. Manual Test Report function. Manual Transmission Clear function. Mounts in a separate enclosure (ABS-8RB or UBS-1). Communicates vital system status including: – Independent zone fire alarm. – Independent zone non-fire alarm.
– Independent zone trouble. – Independent zone supervisory. – AC (mains) Power Loss (programmable). – Low Battery and Earth Fault.
Notifier 3030 Programming Manual
– System Off-Normal. – 12 or 24 hour test signal. – Abnormal Test Signal per new UL requirements. – EIA-485 Communication Bus Failure.
Notifier 500 Programming Manual
Annunciation of UDACT Troubles including: loss of phone lines, communication failure with either Central Station, total communications failure. Troubleshoot Mode converts keypad to DTMF touchpad. Individual LEDs for: Power, EIA-485 Loss, Manual Test, Kissoff, Comm Fail, Primary Line Seize, Secondary Line Seize and Modem Communications. Open Collector relay driver for Total Communications Fail- ure or UDACT trouble. Real-time clock. Extensive transient protection. Simple EIA-485 interface to host panel.
Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL Listed: S635. ULC Listed: CS100 Vol. VII. MEA: 328-94-E; 317-01-E3. CSFM: 7300-0028:174; 7165-0028:214; 7165-0028:224; 7170-0228:216; 7170-0028:223; 7165-0028:243, 7170- 0028:244.
INDUSTRY CANADA: 2132 6030 A. FCC: 1W6-USA-20723-AL-E. FM Approved Communication Formats. 3+1 Standard. 4+1 Standard. 4+2 Standard.
4+1 and 4+2 Ademco Express. Ademco Contact ID UDACT 48 67ud ac.w mf.